Options

Thermostatic mixing valve set for safety showers

Article-No.: BR 710 960

The thermostatic mixing valves of the ComfortLine series are special mixing valves for eye showers and safety showers that ensure highly precise control of the water temperature and scald protection. A continuous supply of hot and cold water is required for this purpose. The thermostatic mixing valves guarantee that the correct water temperature is always available at the tapping point and that unwanted temperature fluctuations are prevented.

Technical Specifications

  • Pressure stage: PN 10
  • Operating pressure: 10 bar
  • Differential pressure mixing: max. 3 bar
  • Differential pressure cold/hot water supply: max. 0,3 bar
  • Differential pressure to trigger the bypass function: min. 0,5 bar
  • Medium temperature: min. 0°C / max. 95°C
  • 160 litres / minute at 1.0 bar differential pressure
  • Flow rate in bypass function: 90 litres / minute at 1.0 bar differential pressure
  • Temperature stability: +/- 5°C (only valid with same pressure at cold/hot water supply)
  • Water inlet: 1 1/4” female
  • Water outlet: 1 1/4” female
  • Dimensions (H x W x D): 300 x 290 x 235 mm

Product description

The scald protection reliably protects the user from scalding. The scald protection comes into play when an uncontrolled overshoot of the hot water temperature occurs or the cold water supply fails.

The thermostatic mixing valve ensures continuous water supply even if the hot water supply fails (e.g. if the hot water is turned off). The function is used when the differential pressure between cold and hot water exceeds 0.5 bar. In this case, cold water escapes at the tapping point (bypass function).

Technical Description

  • Adjustment range 20-43°C, preadjusted to 22°C
  • Automatic check of the cold and hot water supply line
  • hidden water temperature adjustment with scald protection at 43°C
  • Safety shut-off of hot water in case of cold water supply failure
  • Flow rate 160 litres / minute at 1.0 bar differential pressure, flow rate in bypass function 90 litres / minute at 1.0 bar differential pressure
  • Hot water connection 1 1/4” female, cold water connection 1 1/4” female, water outlet 1 1/4” female
  • Integrated backflow preventer in cold/hot water connection to protect the drinking water
  • Dimensions (H x W x D): 300 x 290 x 235 mm
  • according to BGI/GUV-I 850-0, DIN 1988 and EN 1717
  • according to ANSI Z358.1-2014 and EN 15154-2:2006
  • Manufacturer: B-SAFETY or equal

Do you have questions or would you like advice?

We will be happy to answer any questions and look forward to hearing from you.

You can reach us Monday to Thursday from 8 am to 5 pm and Friday from 8 am to 2 pm.

WE LOOK FORWARD TO YOUR MESSAGE

Leave this field blank

CONTACT

B-SAFETY GmbH
Oststraße 85
22844 Norderstedt

info(at)b-safety.com

Do you have questions or need help? Send us an email and we’ll get in touch shortly.